U.S. Compressed-Air Design Rules: ASHRAE 90.1 and the AIM Act

Between 2022 and 2024, two United States references began to show up more often around the compressor room: an ASHRAE energy standard that, for the first time, included compressed-air system requirements, and a federal refrigerant law that phases down the production and import of certain hydrofluorocarbons (HFCs). For teams designing or supplying equipment across regions, the useful question is not a new slogan. It is which requirements are local, which edition or step is actually in force, and which good practices travel better than the statutes themselves.

This article is a reading guide, written in November 2026. It is not a code opinion, not a substitute for the official standard or statute, and not a statement that SIND products, stations, or projects comply with ASHRAE 90.1, the U.S. AIM Act, or any certification program. The rules discussed below apply in the United States, and only where a jurisdiction has adopted the relevant standard edition or where the federal statute already applies. They are not automatically applicable in China or in other markets.

This article is also not about China’s T/CGMA 1203-2026 standard for 0-level compressed-air source evaluation, which is a different document, in a different jurisdiction. The two must not be read as equivalents. See China Releases T/CGMA 1203-2026 Standard for 0-Level Compressed Air Source Evaluation.

ASHRAE 90.1: a U.S. energy standard, not a global code

ANSI/ASHRAE/IES Addendum az to Standard 90.1-2019, approved on 21 January 2022, added Section 10.4.6, “Compressed Air Systems.” That language was incorporated into the 2022 edition of Standard 90.1. An official ASHRAE errata sheet for the 90.1-2022 SI edition, dated 9 February 2026, still revises Section 10.4.6.1, which confirms that the compressed-air section remains part of the 2022 edition as of that errata date. The 2022 SI edition’s first printing is identified in that errata sheet as December 2022 (product code 86329 12/22).

The official addendum is the right place to check scope. In summary, and without reproducing the standard’s text: Section 10.4.6 applies to compressed-air systems in factory industrial occupancies — the compressors, related piping, and controls that provide compressed air — and not to equipment or controls that use or process the air. Medical air systems are excepted. The section then sets requirements, above stated power or size thresholds and with listed exceptions, covering part-load / trim capacity and primary storage, system controls, monitoring, leak testing of piping, and pipe sizing.

A few limits have to stay in the open. First, 90.1 is a standard. It becomes binding only where a state, city, or client has adopted that edition, or a code that references it, and only as adopted — jurisdictions may amend or omit sections. Second, this article does not treat a 2024 trade-journal report as a substitute for the official text. Third, as of November 2026, a 2025 edition of Standard 90.1 has been published; this article does not cite 2025 clause numbers, because the official 2025 text was not reviewed here. Project specifications should follow the edition actually adopted by the authority having jurisdiction.

Nothing in that history is a SIND certification, and “included in 90.1” is not a worldwide requirement.

The U.S. AIM Act is about HFC production and use, not about dryer type

The American Innovation and Manufacturing (AIM) Act was enacted on 27 December 2020. Official U.S. Environmental Protection Agency (EPA) materials state that the Act directs EPA to phase down production and consumption of listed HFCs, in steps, to 15% of historic baseline levels by 2036 — an 85% phasedown — through an allowance program for producing or importing bulk HFCs. EPA’s published schedule, also reflected in 40 CFR Part 84, sets allowance caps at 90% of baseline for 2022–2023, 60% for 2024–2028, 30% for 2029–2033, 20% for 2034–2035, and 15% from 2036 onward. As of this writing, calendar year 2026 falls in the 60%-of-baseline step. EPA issued notice of calendar-year 2026 allowance allocations in 2025.

A 2024 trade article sometimes framed reclaimed or recycled HFCs as simply “unaffected.” That is too crude for a 2026 reader, and it is not used as a legal statement here. Official EPA materials distinguish two tracks. The allowance caps apply to production and consumption of bulk HFCs. Separately, the 2024 Emissions Reduction and Reclamation (ER&R) rule, as described in EPA’s January 2026 fact sheet and frequent-questions page, sets a reclamation standard beginning 1 January 2026: refrigerant sold or identified as reclaimed for installation, servicing, or repair may contain no more than 15% virgin HFCs by weight, and must meet listed purity rules. Beginning 1 January 2029, servicing or repair in certain listed refrigeration subsectors — supermarket systems, refrigerated transport, and automatic commercial ice makers — must use reclaimed HFCs that meet that standard. Those three subsectors are the ones EPA lists for the 2029 servicing requirement. This article does not extend that 2029 list to industrial compressed-air dryers.

The design question that can be asked on a United States inquiry is practical: if the treatment plant includes a refrigerated dryer or a chiller, what refrigerant does it use, and has the local service market been considered for the life of the machine? In other countries, the analogous question is whatever local refrigerant rule actually applies, not a copied AIM Act timetable. This article does not recommend a refrigerant, does not state which refrigerants any SIND equipment uses, and does not claim that any dryer is AIM-Act compliant or “future-proof.”

Performance data and careful assessment are not a substitute statute

Trade articles from 2024 also returned to a less jurisdictional idea: published, comparable performance data, and people who know how to read it, still matter more than a brochure number. Industry data sheets and recognized assessment methods can help a project team compare machines and check how a system is being operated. Those programs have their own current rules and directories, which should be checked on the issuing organization’s site if they are cited in a specification.

None of this should be read as a SIND certification or as a claim that a SIND station meets ASHRAE 90.1. If a project is compared or audited, the honest request is for a recognized data sheet and for an assessment method that can be checked — not for a marketing efficiency percentage.

What did not change

Nothing in the official sources opened for this article creates a worldwide compressed-air energy code, a single acceptable refrigerant, or a requirement that every plant replace its dryers on a 2023–2024 timetable. Nothing in those sources is a stand-in for China’s T/CGMA 1203-2026 work on 0-level source evaluation. A specification that mixed those stories into one “new standard” would mislead readers in both markets.

Related reading on this site

For assessment and control practice, see Auditing a Compressed-Air System, Compressor Group Control: Getting the Sequence Right, and Variable-Frequency Technology in Compressor Energy Upgrades.

Reviewing a U.S. project specification or a cross-border design? Talk to a SIND engineer · Browse product families.

Official and supporting sources. Dates below are the sources’ own dates, not the publication date of this SIND article. This is a short editorial summary, not a reprint of any standard or statute. Project teams should consult the official text and the edition or rule actually in force in the project jurisdiction. No SIND compliance, certification, or refrigerant claim is made.

  1. ANSI/ASHRAE/IES Addendum az to ANSI/ASHRAE/IES Standard 90.1-2019, approved 21 January 2022 (Section 10.4.6, Compressed Air Systems). Official PDF: ashrae.org addendum az. The addendum is copyrighted; this article does not reproduce its text.
  2. ASHRAE, Errata sheet for ANSI/ASHRAE/IES Standard 90.1-2022 (SI Edition), 9 February 2026, including a revision to Section 10.4.6.1; first printing identified as December 2022 (product code 86329 12/22). ashrae.org 90.1-2022 SI errata (9 Feb 2026)
  3. U.S. EPA, “Frequent Questions on the Phasedown of Hydrofluorocarbons,” including the AIM Act phasedown schedule and the 2024 ER&R reclamation questions (page opened 11 November 2026). epa.gov/hfcs FAQ
  4. U.S. EPA, “Phasedown of Hydrofluorocarbons (HFCs): Issuing Allowance Allocations for 2026” (page opened 11 November 2026). epa.gov 2026 allocations
  5. U.S. EPA, “American Innovation and Manufacturing Act: Reclamation Requirements for Hydrofluorocarbon Refrigerants,” fact sheet, January 2026. EPA ER&R reclaim fact sheet (Jan 2026)
  6. 40 CFR Part 84, Phasedown of Hydrofluorocarbons, implementing the AIM Act (see especially the phasedown schedule). Consult the official eCFR or Federal Register text before any compliance decision: eCFR 40 CFR Part 84

Planning a compressed air project?

Talk to an engineer
SIND Applications Engineering

The SIND applications engineering team reviews compressed air duty points, sizes systems and writes the technical articles published on this site.

Published November 12, 2026 · Updated November 16, 2026.

SIND
Jafor Nayan Sales Engineer Biruk Argaw Sales Engineer