A machine shop’s Grade-1 station: 56.5% against a 55.0% threshold
Not every Grade-1 station is a plant-wide rebuild. A machine shop inside a compressor manufacturer had its workshop station graded at Grade-1 in 2022 with a single 125 kW lubricated screw, a refrigerated dryer, precision filters and a controller — a small, well-instrumented system, certified at 56.5% comprehensive output efficiency against a 55.0% threshold for its class.
The narrowness of that margin is the interesting part. Station grading is not a quality award; it is a measurement against a boundary, and a 1.5-point margin means the station has to be maintained to keep its claim.
What the grading scheme measures
The T/CGMA 033001 series, published in October 2018 and effective from January 2019, grades compressed air stations rather than machines, in three levels:
- Grade 1 — described as international advanced practice, lowest energy consumption.
- Grade 2 — comparatively energy-efficient.
- Grade 3 — representative of the domestic market average.
Two quantities underlie it. Specific electricity consumption is the electricity used per unit volume of air delivered, referred to intake conditions. Comprehensive output efficiency compares useful compression work delivered — pressure and flow at the station outlet — with the station’s total electrical input. The latter is the grading figure because it captures delivered pressure as well as volume.
For a lubricated screw station in this class, the Grade-1 threshold sits at 55.0%. This station measured 56.5%.
The equipment list that produced it
- Compressor: one 125 kW micro-oil screw rated at 8 bar.
- Treatment: a refrigerated dryer, plus a high-efficiency precision filter set.
- Instrumentation: a smart electricity meter on the station, and a pitot-tube differential-pressure flow meter on the delivery.
- Control: a station controller sequencing the machine and the treatment equipment, with a visualised energy dashboard and automatic load balancing.
That list is unremarkable, and that is the point. The station was not built with exotic equipment; it was built with a complete measurement chain and a control layer. A station cannot be graded if its flow and power cannot be measured at the boundary, and in most plants they cannot.
Why the flow meter matters more than the compressor
Specific power at the machine is a catalogue figure. Comprehensive output efficiency at the station boundary is a measurement, and it depends on instruments installed at specific points:
- Electrical input at the station, including the dryer and controls, not just the compressor.
- Flow at the delivery point, measured in a way that survives a fluctuating load — differential pressure across a pitot element is a common choice because it tolerates dirt better than some alternatives, but it needs its own calibration.
- Pressure at the same point, because delivered pressure is half the definition.
A station measured at three points on three different days is not a measurement of anything.
Maintenance is part of the grade
A station sitting 1.5 points above its threshold is sensitive to the things that degrade quietly:
- Filter pressure drop rises with loading; a dirty element can cost several tenths of a bar.
- Dryer performance falls as the condenser fouls, especially in summer.
- Sequencing drift — a controller left in manual, or a set point nudged — moves the efficiency figure without any component failing.
- Leakage raises the flow at a given production level, which lowers the efficiency ratio directly.
Certification therefore implies an operating discipline, not just a capital project: keep the filters changed, keep the dryer clean, keep the controller in automatic, and keep the leak register alive.
The pattern
The reported result — 56.5% with a 55.0% threshold — describes a station where the measurement was designed in from the start. That is the transferable lesson for a plant of any size: the marginal cost of the meters and the controller is small relative to the compressor, and without them the station has no performance figure at all, only a nameplate.
—
Industry practice note. Facts as reported by industry press; the station described is not a SIND project.
Planning a compressed-air upgrade? Talk to SIND’s engineers.
Facts as reported by industry press; the project described is not a SIND project.
Planning a compressed air project?
Talk to an engineerPublished November 16, 2026.